SES locations

Unacceptable SES locations

The information below can also be found in the Electric Service Specifications section 9.

For reasons of public safety and maintenance of service, it is not permissible to install SES equipment as follows:

  1. In locations that are not readily accessible.
  2. Within substations or transformer vaults containing SRP transformers and equipment.
  3. In locations hazardous to personnel.
  4. On surfaces subject to excessive vibration.
  5. Inside rest, bath, shower, powder or toilet rooms.
  6. In an elevated or depressed area that does not have access provided by means of a ramp or clear stairway of normal tread and rise in conformance to building code requirements.
  7. In an unsanitary area in reference to farm animals and products.
  8. On SRP poles or other SRP facilities.
  9. Within twenty (20) ft. of any gas pump and within ten (10) ft. of any gas storage tank, fill spout and/or vent.
  10. Within 36" of any gas meter vent.
  11. Within parking structure, unless approved by Distribution Design.

Back to top

Accessible SES locations

The information below can also be found in the Electric Service Specifications section 1. The following term, when used herein, shall have the meaning specified.

  • Readily accessible: See current Electric Service Specifications manual, Section 1 - Definitions.

You can find the entire Electric Service Specifications here

Back to top