SES locations
The information below can also be found in the Electric Service Specifications section 9-6.
For reasons of public safety and maintenance of service, it is not permissible to install SES equipment
as follows:
- In locations that are not readily accessible.
- Within substations or transformer vaults containing SRP transformers and equipment.
- In locations hazardous to personnel.
- On surfaces subject to excessive vibration.
- Inside rest, bath, shower, powder or toilet rooms.
- In an elevated or depressed area that does not have access provided by means of a ramp or clear stairway of normal tread and rise in conformance to building code requirements.
- In an unsanitary area in reference to farm animals and products.
- On SRP poles or other SRP facilities.
- Within twenty (20) ft. of any gas pump and within ten (10) ft. of any gas storage tank, fill spout and/or vent.
- Within 36" of any gas meter vent.
- Within parking structure, unless approved by Distribution Design.

The information below can also be found in the Electric Service Specifications section 1-6. The following term, when used herein, shall have the meaning specified.
- Readily accessible: Capable of being reached directly, without obstruction at any time. A direct (without bends) unobstructed access to the Service Entrance Section shall be provided and maintained that is a minimum 12 ft. wide and 20 ft. high, suitable for line construction equipment. A bend in the access route is allowed if the width is increased to 20 ft. A customer-provided and maintained removable screen wall, panel or door, with a minimum width of 20 ft., may be used as an architectural feature, provided the access route complies with the requirements listed above.