Sub Panel

|
| Thermal Image Data |
| IR File Name |
C0605-14.img |
| Date of IR Image |
6/5/02 |
| Time of IR Image |
10:39:51 AM |
| Ambient Temperature |
26.4°F |
| Hot Spot |
57.8°F |
| Reference Spot |
44.91°F |
| Temperature Difference |
13°F |
| Priority Rating from table below |
2 |
| Comments |
| Breaker warmer than expected with 6 amps through each pole. Check breaker and terminations. |
|
| Priority Rating Table |
| |
Temperature difference (delta T) based on comparisons between similar components under similar loading
|
Temperature difference (delta T) based on comparisons between component and ambient air temperature
|
Recommended Action |
| 1 |
1 - 3 F |
1 - 10 F |
Possible deficiency; warrants investigation |
| 2 |
4 - 15 F |
11 - 20 F |
Indicates probable deficiency; repair as time permits |
| 3 |
|
21 - 40 F |
Monitor continuously until corrective measures can be started |
| 4 |
>= 16 F |
> 40 F |
Major discrepancy; repair immediately |
|
N.E.T.A. Maintenance Testing Specifications, for electrical equipment used for priority rating table.
|
|