Motor

|
| Thermal Image Data |
| IR File Name |
C0809-03.img |
| Date of IR Image |
8/9/2002 |
| Time of IR Image |
7:41:25 AM |
| Ambient Temperature |
78.7°F |
| Hot Spot |
114.9°F |
| Reference Spot |
109.3°F |
| Temperature Difference |
36°F |
| Priority Rating from table below |
4 |
| Comments |
| Inboard motor bearing significantly warmer than the rest of the motor. |
|
| Priority Rating Table |
| |
Temperature difference (delta T) based on comparisons between similar components under similar loading
|
Temperature difference (delta T) based on comparisons between component and ambient air temperature
|
Recommended Action |
| 1 |
2 - 5 F |
2 - 18 F |
Possible deficiency; warrants investigation |
| 2 |
7 - 27 F |
20 - 36 F |
Indicates probable deficiency; repair as time permits |
| 3 |
|
38 - 72 F |
Monitor continuously until corrective measures can be started |
| 4 |
>= 29 F |
> 72 F |
Major discrepancy;repair immediately |
|
N.E.T.A. Maintenance Testing Specifications, for electrical equipment used for priority rating table.
|
|